Go top
Paper information

On the use of a convex model for bulk storage in mip-based power system operation and planning

J.M. Arroyo, L. Baringo, A. Baringo, R. Bolaños, N. Alguacil, N. G. Cobos

IEEE Transactions on Power Systems Vol. 35, nº. 6, pp. 4964 - 4967

Summary:

Recently, several authors have reported specific criteria to support the widely accepted use of a convex operational model for bulk energy storage in the formulation of power system operation and planning problems involving binary variables. Using two counterexamples, we show that this modeling simplification may give rise to impractical solutions featuring simultaneous charging and discharging, even though the recently published criteria are satisfied. Thus, both counterexamples invalidate those criteria and demonstrate that the customarily used convex model may be unsuitable for the precise incorporation of bulk storage in such instances of mixed-integer programming.


Keywords: Convex operational model, electrical energy storage, power system operation and planning with binary variables, simultaneous charging and discharging.


JCR Impact Factor and WoS quartile: 6,663 - Q1 (2020); 6,600 - Q1 (2022)

DOI reference: DOI icon https://doi.org/10.1109/TPWRS.2020.3020730

Published on paper: November 2020.

Published on-line: September 2020.



Citation:
J.M. Arroyo, L. Baringo, A. Baringo, R. Bolaños, N. Alguacil, N. G. Cobos, On the use of a convex model for bulk storage in mip-based power system operation and planning. IEEE Transactions on Power Systems. Vol. 35, nº. 6, pp. 4964 - 4967, November 2020. [Online: September 2020]